Electrical Load Center May Overheat – 2019-2021 E-One Cyclone 2, 2020 Commercial, Quest 2, 2020-2021 Typhoon, 2021 Cyclone N, & 2020-2022 Typhoon N Fire Trucks

“This site contains affiliate links for which OEMDTC may be compensated”

July 26, 2022 NHTSA CAMPAIGN NUMBER: 22V538000

Electrical Load Center May Overheat

An overheated load center can increase the risk of a fire.

 

NHTSA Campaign Number: 22V538

Manufacturer E-OneeBay Incorporated

Components ELECTRICAL SYSTEM

Potential Number of Units Affected 78

 

Summary

E-OneeBay Incorporated (E-OneeBay) is recalling certain 2019-2021 Cyclone 2, 2020 Commercial, Quest 2, 2020-2021 Typhoon, 2021 Cyclone N, and 2020-2022 Typhoon N fire trucks. The neutral screw connection within the QO Plug-On Neutral Load Center may be loose. If that connection is loose, the affected load center can overheat.

 

Remedy

Dealers will inspect and repair, or replace the load center, free of charge. Owner notification letters were mailed October 24, 2022. Owners may contact E-OneeBay’s customer service at 1-352-237-1122.

 

Notes

Owners may also contact the National Highway Traffic Safety Administration Vehicle Safety Hotline at 1-888-327-4236 (TTY 1-800-424-9153), or go to www.nhtsa.gov.

 


TO: Electrical Contactors and Homebuilders

FROM: Schneider Electric (SE) Recovery Administration

SUBJECT: QOTM Plug-On Neutral Load Center

RE:

1. Product Identification and Quarantine
2. Product Inspection and Remediation
3. Product Return
4. Request for Customer List Ref.: PRB-236759

 

RECALL SAFETY NOTICE

NOTICE OF POTENTIAL UNSAFE CONDITION

PLEASE DELIVER IMMEDIATELY TO THE RESPONSIBLE PERSON IN YOUR ORGANIZATION

 

Dear Valued Customer,

Schneider Electric is committed to delivering high quality products to our customers. As part of our ongoing quality monitoring process, a potential issue was detected that may affect specific QO Plug-On Neutral Load Centers manufactured between February 1, 2020 and January 12, 2022 at Schneider Electric Plant 15.

The issue detected is a loose neutral screw connection within the QO Plug-On Neutral Load Center. If that connection is loose, the affected load center can overheat, posing thermal burn and fire hazards There is a potential for PROPERTY DAMAGE AND PERSONAL INJURY as a result.

Affected products were manufactured between February 1, 2020 and January 12, 2022, with date codes between 200561 and 220233. Plant 15 is the only plant impacted and all other plant codes are not affected. A complete list of affected catalog numbers, date code description, and inspection instructions is shown in Attachment 1, Product Identification.

This nonconformity has been contained at Schneider Electric manufacturing plants, distribution centers and product adaptation locations. All QO Plug-On Neutral Load Centers produced after January 12, 2022 are conforming to Schneider Electric design and manufacturing standards.

Existing inventory with date codes prior to January 13, 2022 has been validated and is marked with a green dot to indicate compliance with Schneider Electric design and manufacturing standards. Any product marked with a green dot on the carton is excluded from this notice.

This Product Recall is happening in cooperation with and has approved by the Consumer Product Safety Commission (“CPSC”).

This letter is to communicate these risks and outline actions requested to ensure the proper identification, quarantining and return of any affected product.

While the inconvenience is regrettable, safety remains the highest priority of Schneider Electric. For this reason, thank you for your prompt assistance in this matter.

 

What to do: 

Inspect existing inventory and stop installation of the affected products immediately.

If this activity has not been completed, please do so immediately. All affected  products should be removed from stock and/or shelves and quarantined in accordance with attachment 1.

 

If continued quarantining of affected product is not feasible, please contact SE   customer care department for further assistance at 888-778-2733 options 2, 1, 4.

 

How to Identify Affected Product – Not Installed

To properly identify a potentially affected QO Plug-On Neutral Load Centers using the information on the carton, please refer to Attachment 1, Part I – Outdoor Product Identification, and Part II – Indoor Product Identification.

 

How to Identify Affected Product – Installed

Once a product has been installed, the catalog number and date code may only be found inside the enclosure, on the identification labels.

 

Only qualified electrical individuals should remove the cover of the load center.

Please refer to Attachment 1, Part III – Product out of Carton for the location and information to be found on the product labels.

 

How to Inspect Products – Not Installed

Schneider Electric has developed a list of instructions for inspection of a product. It is recommended that these instructions be carried out only by properly trained and licensed professionals.

To receive a copy of these instructions, follow the Inspection Link

 

How to Inspect (and Possibly Repair) Products – Installed

Schneider Electric has developed a list of instructions for the inspection, and possible remediation of an installed and connected load center. These instructions must only be followed by trained and licensed professionals.

To arrange for an inspection of a load center, please contact Schneider Electric via the General Questions and Technical Support contact information above.

Trained professionals may receive a copy of these inspection instructions by contacting Schneider Electric. The Customer Care team will register any professional and send a copy of the instruction for inspection and possible repair of installed load centers. Please contact us via the General Questions and Technical Support contact information above.

 

Customer Contact Information

SE desires to contact all customers who have purchased the affected product. To the extent allowable by law, please provide any customer contact information so SE may notify any known customers directly.

All customer information provided to SE will only be utilized for the purposes of this Product Safety Alert.

SE requests the name(s) and address(es) of the customer(s) who have purchased affected product by either providing an excel spreadsheet or through the following link provided.

For Further Customer Questions:

If a customer has any further questions concerning affected product, please refer to the following contact information;

General Questions and Technical Support

chat at MySE/MySchneider or

https://www.se.com/us/en/work/support/customer-care/contact-schneider- electric.jsp

Phone: 888-778-2733 options 2, 1, 4

Email: technicalsupport@schneider-electric.com

To return affected product either from a store or a customer , please refer to the following contact information;

 

Returns

Chat through MySE/MySchneider

Phone: 888-778-2733 option 3

Email: ccc-claims@schneider-electric.com

How to identify affect product

To properly identify a potentially affected QO Plug-On Neutral Load Centers, please refer to Product Identification.

 

Product Identification

Table 1 –     US Stocked Products — Affected Catalog Numbers 

QO112L125KPCAQO124M125PRBQO142M150PC
QO112L125PGQO124M150PQO142M200P
QO112L125PGCQO124M200PQO142M200PC
QO112L125PGRBQO124M200PWG125QO142M200PCAFVP
QO112L125PWGQO130L125PGQO142M200PCVP
QO112L125VPCAQO130L125PQGQO142M200PQ
QO112L200PGQO130L150PGQO142M200PQCVP
QO112L200PGRBQO130L200PGQO142M200PRB
QO112M100PQO130L200PGCQO142M225P
QO112M100PCQO130L200PGRBQO142M225PRB
QO112M100PRBQO130L200PQGQO142MQ200PQ
QO116L125PGQO130L200PWGQO154L225PG
QO116L125PGRBQO130M150PQO154L225PGC
QO116M100PQO130M150PCQO154L225PGMF
QO116M100PCQO130M150PRBQO154L225PQG
QO116M100PRBQO130M200PQO154M200P
QO120L125PGQO130M200PCQO154M200PC
QO120L125PGCQO130M200PQQO154M200PQ
QO120L125PWGQO130M200PRBQO160M200PC
QO120M100PQO132L125PGQO1816M200PFTRB
QO120M100PCQO132M100PQOGP3P3036P
QO120M100PRBQO132M100PCVPQOGP3P6036P
QO120M150PQO132M125PQOGP3P604436100P
QO120M150PRBQO132M150PQOGP3P604436125P
QO120M200PQO140L200PGQOGP3P604436150P
QO120M200PRBQO140L200PGRBQOGP3P604436200P
QO124L125PGQO140L225PGQON112L125PI
QO124L125PGCQO140M200PQON112L200PI
QO124L125PGCVPQO140M200PCQON120L125PI
QO124L125PGRBQO140M200PCBEQON124L200PDL
QO124L125PQGQO140M200PRBQON124L200PI
QO124L125PQGCVPQO140M200PT2QON130L200PDL
QO124L200PGQO140M225PQON130L200PI
QO124M100PQO142L225PGQON142L225PI
QO124M100PCQO142L225PGCQON154L225P
QO124M100PCVPQO142L225PGCVPQON160L225P
QO124M100PRBQO142L225PGRB
QO124M125PQO142L225PQG

 

Table 2 –     Canada Stocked Products – Affected Catalogue Numbers

CQO112L100PGCCQO124M100PCCQO140L125PGC
CQO112M100PCCQO124M100PCDCQO140L200PGC
CQO112M30PCCQO124M100PRBCQO140L200PGRB
CQO112M40PCCQO124M30PCCQO140M100PC
CQO112M50PCCQO124M40PCCQO140M125PC
CQO112M60PCCQO124M50PCCQO140M150PC
CQO112M70PCCQO124M60PCCQO140M200PC
CQO116L100PGCCQO124M70PCCQO140M200PCD
CQO116L100PGRBCQO132L125PGCCQO140M200PRB
CQO116M100PCCQO132L200PGCCQO140M60PC
CQO116M100PRBCQO132M100PCCQO142L225PGC
CQO116M30PCCQO132M100PCDCQO160L225PGC
CQO116M50PCCQO132M125PCCQO160M100PC
CQO116M60PCCQO132M150PCCQO160M125PC
CQO116M60PRBCQO132M200PCCQO160M150PC
CQO124L125PGCCQO132M60PCCQO160M200PC
CQO124L125PGRBCQO132M70PCCQO160M225PC
QP24100
QP32100
QP32100
QP32100

 

Inspection Workflow

Is my catalog number affected? 1 ⇒ NoProduct is not impacted by Safety Notice

Does Plant Code = Plant 15 on label? ⇒ No ⇒ Product is not impacted by Safety Notice

Is there a Green Dot on the box? ⇒ No ⇒ Product is not impacted by Safety Notice

Is date code on product within scope? ⇒ No ⇒ Product is not impacted by Safety Notice

Yes

Contact SE for repair

1 Affected catalog numbers can be found on the customer letter and/or the website: https://se.com/us/qoloadcneter-safetyrecallnotice

 

Outdoor Load Center

1

Step 1 — Catalog Number

Validate if catalog number is within scope of safety notice. Refer to customer letter and/or URL: https://se.com/us/qoloadcneter-safetyrecallnotice

 

2

Step 2 — Plant Code

Validate Plant Code = Plant 15. Confirm if Plant Code in square box = 15. If no, product is unaffected by safety notice. If yes, proceed to Step 3.

 

3

Step 3 — Green Dot

Validate if a Green Dot is present on the label. If yes, product is unaffected by safety notice. If no green dot is present, proceed to Step 2.

 

4

Step 4 — Date Code

Validate the date code is within scope of the safety notice. Date code is translated as:

YYWWDS. YY=Year; WW=Week; D=Day of the week; S=Shift.

Example Shown:

  • Date Code = 221111
  • Year 22, Week 11, Day 1, Shift 1
  • Date = March 7, 2021 Shift 1

If date code is earlier than January 13, 2022, then the product is within scope of the safety notice and is affected.

 

Indoor Load Center

1

Step 1 — Catalog Number

Validate if catalog number is within scope of safety notice. Refer to customer letter and/or URL: https://se.com/us/qoloadcneter-safetyrecallnotice

 

2

Step 2 — Plant Code

Validate Plant Code = Plant 15. Confirm if Plant Code in square box = 15. If no, product is unaffected by safety notice. If yes, proceed to Step 3.

 

3

Step 3 — Green Dot

Validate if a Green Dot is present on the label. If yes, product is unaffected by safety notice. If no green dot is present, proceed to Step 2.

 

4

Step 4 — Date Code

Validate the date code is within scope of the safety notice. Date code is translated as:

YYWWDS. YY=Year; WW=Week; D=Day of the week; S=Shift.

Example Shown:

  • Date Code = 214531
  • Year 21, Week 45, Day 3, Shift 1
  • Date = November 3, 2021 Shift 1

If date code is earlier than January 13, 2022, then the product is within scope of the safety notice and is affected.

 

Product out of Carton

1

Step 1 — Locate Label

Locate label to identify the load center.

2

Step 2 — Catalog Number

Validate if catalog number is within scope of safety notice. Refer to customer letter and/or URL: https://se.com/us/qoloadcneter-safetyrecallnotice

 

3

Step 3 — Plant Code

Validate Plant Code = Plant 15.

Confirm if Plant Code in square box = 15. If no, product is unaffected by safety notice. If yes, proceed to Step 3.

4

Step 4 — Date Code

Validate the date code is within scope of the safety notice. Date code is translated as: YYWWDS. YY=Year; WW=Week; D=Day of the week; S=Shift. The Date Code is on the label above the Square D logo. If date code is earlier than January 13, 2022, then the product is within the scope of the safety notice and is affected.

 

Schneider Electric USA, Inc.
800 Federal Street
Andover, MA 01810 USA 888-778-2733
www.se.com/us

 


Chronology :

Refer to Recall 22-159 by the Consumer Product Safety Commission (“CPSC”) for Schneider Electric’s chronology.

On July 14, 2022, E-ONEeBay received communication from Schneider Electric about CPSC recall 22-159 for their Square D. Reviewed potential population. Escalated the issue to REV Group Management.

July 22, 2022 – REV’s senior leadership approved a voluntary recall for this issue.

 


11 Affected Products

Vehicles

MAKEMODELYEAR
E-ONEeBayCOMMERCIAL2020
E-ONEeBayCYCLONE II2019-2021
E-ONEeBayCYCLONE N2021
E-ONEeBayQUEST II2020
E-ONEeBayTYPHOON2020-2021
E-ONEeBayTYPHOON N2020-2022

 


9 Associated Documents

Recall Acknowledgement

RCAK-22V538-1177.pdf 645.779KB

Loader Loading...
EAD Logo Taking too long?

Reload Reload document
| Open Open in new tab

Download [630.64 KB]

 


Defect Notice 573 Report

RCLRPT-22V538-7362.PDF 216.097KB

Loader Loading...
EAD Logo Taking too long?

Reload Reload document
| Open Open in new tab

Download [211.03 KB]

 


Miscellaneous Document

RMISC-22V538-0504.pdf 758.272KB

Loader Loading...
EAD Logo Taking too long?

Reload Reload document
| Open Open in new tab

Download [740.50 KB]

 


Recall 573 Report- 08/18/2022

RCLRPT-22V538-3851.PDF 216.095KB

Loader Loading...
EAD Logo Taking too long?

Reload Reload document
| Open Open in new tab

Download [211.03 KB]

 


Remedy Instructions and TSB

RCRIT-22V538-0957.pdf 3716.376KB

Loader Loading...
EAD Logo Taking too long?

Reload Reload document
| Open Open in new tab

Download [3.54 MB]

 


ISSUED Owner Notification Letter(Part 577)

RCONL-22V538-2097.pdf 165.993KB

Loader Loading...
EAD Logo Taking too long?

Reload Reload document
| Open Open in new tab

Download [162.10 KB]

 


Late Owner Letter Mailing

RMISC-22V538-7073.pdf 111.435KB

Loader Loading...
EAD Logo Taking too long?

Reload Reload document
| Open Open in new tab

Download [108.82 KB]

 


Recall Quarterly Report #1, 2022-4

RCLQRT-22V538-4457.PDF 211.122KB

Loader Loading...
EAD Logo Taking too long?

Reload Reload document
| Open Open in new tab

Download [206.17 KB]

 


Recall Quarterly Report #2, 2023-1

RCLQRT-22V538-5814.PDF 211.22KB

Loader Loading...
EAD Logo Taking too long?

Reload Reload document
| Open Open in new tab

Download [206.27 KB]

 


Latest Recalls Documents

 


 

Bestseller No. 1
Square D by Schneider Electric QO2L30SCP QO 30 Amp 2-Space 2-Circuit Indoor Main Lug Load C, Pack of 1, No Color
  • 30A Main Lugs Load Center
  • Surface Mount, 2 Space Circuit
  • 2 Single Poles
  • Solid Neutral Single Phase
  • Cover Included
Bestseller No. 2
Square D - HOM612L100RBCP Homeline 100 Amp 6-Space 12-Circuit Outdoor Main Lugs Load Center
  • 100A Main Lugs Load Center
  • Rainproof, 6 Space Circuit
  • 12 Single Poles
  • As Service Entrance, Use Ground Bar PK7GTA
  • Returns will not be honored on this closeout item
Bestseller No. 3
BIPIMIFI RV Electrical Panel Wf-8930/50NPB, 50 Amp AC Distribution Center, 27 Circuits, Plastic & Polycarbonate (PC) Material
  • [Versatile RV Power Solution]: The Wf-8930/50 Series Can Be a 50 Amp Or 30 Amp Ac Distribution Center, Input Voltage/Hz: 120 Vac Or 240 Vac.
  • [Compact And Lightweight Design]: With Dimensions Of 13.75in x 9.5in x 4in .And a Weight Of Just 3.75 Lbs, This RV Electrical Panel Is Designed For Easy Installation Without Taking Up Valuable Space In Your RV
  • [Quiet Operation]: Engineered For Silent Performance, The Wf-8930/50Npb Operates Without Causing Interference To Other Electronic Devices, Providing a Peaceful Environment While You Enjoy Your Journey
  • [Flexibility]:It Has 15 Available Dc, And Up To 12 Ac, Branch Circuits. The 8930/50 NPB Can Be Coupled With Any Of The Wf-9800 Switch Mode Converters With 55, 65, Or 75 Amps, Which Gives Engineers More Flexibility In Product Design
  • [Reliable After-Sales Support]: We Provide a Range Of After-Sales Services, If You Have Any Questions About The Product, You Can Contact Us
Bestseller No. 4
Square D by Schneider Electric HOM612L100SCP Homeline 100 Amp 6-Space 12-Circuit Indoor Surface, No Size, No Color
  • 100A Main Lugs Load Center
  • Surface Mount
  • 6 Space Circuit - 12 Single Poles
  • As Service Entrance, Use Ground Bar PK7GTA-1
  • Returns will not be honored on this closeout item
SaleBestseller No. 5
SIEMENS View-Pak E0204ML1060SU Indoor Main Lug Load Center, 60 A, Gray
  • The product is good to use
  • The product is of high quality
  • Manufactured in China
Bestseller No. 6
Square D - HOM24L70RBCP Homeline 70-Amp 2-Space 4-Circuit Outdoor Main Lugs Load Center
  • 70A Main Lugs Load Center
  • Rainproof, 2 Space Circuit
  • 4 Single Poles
  • As Service Entrance, Use Ground Bar PK4GTA
  • Includes a rainproof outdoor cover and is for use as a main lug load center in fixed applications
Bestseller No. 7
Square D - HOM1224L125PC Homeline Load Center with Cover, Gray, 125-Amp Convertible Main Lugs, 1-Phase, 12-Space 24-Circuit, Indoor, Plug-on Neutral Ready
  • Includes a fully distributed neutral bar, allowing for the installation of Homeline Plug-on Neutral combination arc fault breakers on any space
  • Each pole space accepts full-size, tandem or quad breakers
  • Ground and neutral bars accept up to (3) #10-14 equipment grounds
  • Includes a combination flush/surface cover and is convertible to main breaker load center with a QOM1 main breaker (sold separately)
  • Accommodates plug-on secondary surge arrestor (sold separately)
SaleBestseller No. 8
SIEMENS W0816ML1125CU 125 amp, 8 Space, 16 Circuit, Outdoor Center Load Cente , Gray
  • Item Weight: 13.0 lb
  • Country of Origin: United States
  • Brand name: SIEMENS
  • Item Dimensions: 15.5"L x 13.0"W x 5.3"H
Bestseller No. 9
SIEMENS P1224L3125CU 125-Amp 12-Space 24-Circuit 3-Phase Main Lug Load Center
  • Three phase 125 Amp main lug load center with 12 spaces/24 circuits
  • Features Siemens patented insta-wire technology which allows for quick and easy installation because screws are already backed out, ready for wire insertion on ground and neutral bars
  • Copper bus
  • All devices are provided with 2 factory installed ground bars
  • Mounting tabs on the trim hold the load center in place freeing up both hands to drive the trim screws
SaleBestseller No. 10
RVGUARD RV Temporary Power Outlet Panel with Breaker, ETL Listed 20 30 50 Amp RV Receptacle, Type 3R RV Electrical Outlet Panel with 20 Amp 90 Degree Adapter Cord for RV, Camper, Travel Trailer
  • Ensure Safety: RVGUARD Temporary power outlet panel is equipped with 50 amp, 30 amp and 20 amp receptacles. One power box for multiple electricity needs. Each outlet is equipped with a strictly matched circuit breaker. Others use breakers that have a higher current rating than the outlet itself, which may cause a potential fire hazard and overheating!
  • ETL Listed: Our entire product is ETL certified, providing a higher level of safety for your RV compared to other brands that only have UL certification for their receptacles.
  • Ready To Install: Each circuit breaker and receptacle is pre-wired and assembled, saving installation time. The power box cover can remain open at 90 degrees, so you don't have to hold the cover when wiring. And we have reserved enough mounting holes on the back of the power panels for easy installation and hanging.
  • Weatherproof & Durable: Enclosure Protection Degree: TYPE 3R. The power outlet box is constructed of heavy-duty metal with powder coating, making it stronger and more wear-resistant, the waterproof electrical box can keep your equipment well-protected and more efficient in harsh environments.
  • Large Space & Lockable: This RV Power Outlet Panel features a large inner space design, it is wide enough to close the cover while plugging in. You can lock the box with the lock to ensure the children's safety.

 


Last update on 2025-04-17 / Affiliate links / Images from Amazon Product Advertising API


 

This product presentation was made with AAWP plugin.

Leave a Comment

Share to...