NHTSA ID Number: 10110548
Manufacturer Communication Number: SMB123
Summary
Service Manual Bulletin – Preventative Maintenance – Amerex Fire Suppression & Gas Detection Systems
1 Affected Product
Vehicle
SMB-123B
ISSUE DATE: Jun 06 2013
Amerex Fire Suppression & Gas Detection Systems
PM – Preventive Maintenance
This bulletin has been issued to raise Operator awareness of the scheduled preventive maintenance activities necessary to support both the Amerex Fire Suppression and Gas Detection Systems used on your New Flyer
vehicle.
This information supersedes all prior information on this subject already provided in your New Flyer
Manuals. Make this Service Bulletin available to service personnel to inform them of changed information.
SMB123 dated May 07 2013 has been revised to:
❒ Mod III System – delete requirement to test the alarm and LED functions from Daily Preventive Maintenance.
❒ Mod III System – add requirement to test the alarm and LED functions to Monthly Preventive Maintenance.
❒ AVSD System – delete requirement to test the alarm and LED functions and the test relay operations from Daily Preventive Maintenance.
SEOCONTENT-START
SMB-123B Copyright © 2013 New Flyer
Industries Canada ULC Cover
SERVICE MANUAL BULLETIN
This Service Manual Bulletin is prepared by the Publications Department of New Flyer
Industries
Canada ULC. Refer to details below.
ISSUE DATE: Jun 06 2013
SMB-123B
APPLICABILITY
VEHICLE LENGTH ???? 30ft. ???? 35ft. ???? 40ft. ???? 60ft. ???? ALL
VEHICLE TYPE ???? High Floor ???? Low Floor ???? Invero ???? Xcelsior ???? ALL
FUEL TYPE
???? Diesel ???? Electric ???? CNG ???? LNG
???? ALL
???? Diesel/Electric ???? Gas/Electric ???? Fuel Cell
SUBJECT Amerex Fire Suppression & Gas Detection Systems
SECTION TITLE PM – PREVENTIVE MAINTENANCE
INITIAL DETAILS This bulletin has been issued to raise Operator awareness of the scheduled
preventive maintenance activities necessary to support both the
Amerex Fire Suppression and Gas Detection Systems used on your New
Flyer vehicle.
This information supersedes all prior information on this subject already
provided in your New Flyer
Manuals. Make this Service Bulletin available
to service personnel to inform them of changed information.
REV B DETAILS SMB123 dated May 07 2013 has been revised to:
❒ Mod III System – delete requirement to test the alarm and LED
functions from Daily Preventive Maintenance.
❒ Mod III System – add requirement to test the alarm and LED functions
to Monthly Preventive Maintenance.
❒ AVSD System – delete requirement to test the alarm and LED
functions and the test relay operations from Daily Preventive
Maintenance.
SMB-123B Copyright © 2013 New Flyer
Industries Canada ULC 1 of 5
SERVICE MANUAL BULLETIN
SMB-123B
1. Amerex Fire Suppression &
Gas Detection Systems
1.1. Purpose
This bulletin is issued to ensure that all
users are aware of the preventive maintenance
requirements necessary to support
the Fire Suppression and Gas Detection
Systems. The preventive maintenance
schedule covers the following Amerex Systems:
❒ Modular III Fire Suppression – Amerex
Manual Number 13980, and Number
19680
❒ Amerex Vehicle Safety Net (AVSN) Fire
Suppression – Amerex Manual Number
13980, and if equipped with optical sensors,
Number 16601.
❒ AMGaDS Fire Suppression & Gas Detection
– Amerex Manual Number 14475.
❒ Amerex Vehicle Safety Net (AVSN) Gas
Detection – Amerex Manual Number
16601.
1.2. Preventive Maintenance
☞NOTE:
Amerex manuals must be used in conjunction
with the basic information contained
within this Bulletin to fully comply with all
preventive maintenance requirements.
1.2.1. Preventive Maintenance Schedule
The following table provides an overview of
the scheduled maintenance intervals and
the systems affected. Refer to the specific
maintenance interval and applicable
Amerex manual(s) associated with each
system for detailed maintenance requirements.
PREVENTIVE MAINTENANCE SCHEDULE
DAILY MONTHLY SIX MONTHS THREE YEARS SIX YEARS
Modular III Fire
Suppression
System
Modular III Fire
Suppression
System
Modular III Fire
Suppression
System
Modular III Fire
Suppression
System
Modular III Fire
Suppression
System
AVSN Fire
Suppression
System
AVSN Fire
Suppression
System
AVSN Fire
Suppression
System
AVSN Fire
Suppression
System
AVSN Fire
Suppression
System
AMGaDS Fire
Suppression
System
AVSN Gas
Detection System
AVSN Gas
Detection System
AMGaDS Fire
Suppression
System
AMGaDS Fire
Suppression
System
AMGaDS Fire
Suppression &
Gas Detection
System
2 of 5 Copyright © 2013 New Flyer
Industries Canada ULC SMB-123B
SERVICE MANUAL BULLETIN
SMB-123B
1.3. Daily Preventive Maintenance
1.3.1. Modular III Fire Suppression System
Check the operational status of the fire
suppression system on a daily basis:
❒ Inspect the control panel and confirm that
the SYSTEM OK green LED is illuminated.
❒ Confirm that the FIRE, RELAY RESET,
and SERVICE SYSTEM LED’s are extinguished
☞NOTE:
DO NOT operate the vehicle if either the
FIRE, RELAY RESET, or SERVICE SYSTEM
LED’s are illuminated. Contact service
personnel to investigate the cause.
1.3.2. AVSN Fire Suppression System
Check the operational status of the fire
suppression system on a daily basis. Set
the Master Run switch to DAY-RUN and
observe the display panel for the following:
❒ The display should read “System OK”
immediately following self-configuration.
❒ Confirm that the system POWER green
LED is illuminated.
❒ Confirm that both the FIRE red LED and
TROUBLE yellow LED are extinguished.
❒ Confirm that both GAS CONCENTRATION
LED’s (if equipped) are extinguished.
❒ Confirm that the RELAY RESET red LED
is extinguished
☞NOTE:
DO NOT operate the vehicle if any of the
red or yellow LED’s are illuminated. Contact
service personnel to investigate the
cause.
SMB-123B Copyright © 2013 New Flyer
Industries Canada ULC 3 of 5
SERVICE MANUAL BULLETIN
SMB-123B
1.4. Monthly Preventive Maintenance
1.4.1. Modular III or AVSN Fire Suppression
System
❒ Open access door behind streetside rear
light panel to access gauge. See “Fig. 1:
Fire Suppression Cylinder Inspection” on
page 3.
❒ Check pressure gauge on agent cylinder to
ensure it is in the operating (green) range.
❒ Check all nameplates and instructional
labels for legibility.
❒ Check physical condition of all components
for mechanical damage and security
of mounting.
❒ Check nozzles of agent cylinder. Nozzle
outlets must be free of obstructions. Blowoff
caps must be intact and secure.
❒ Ensure pull pin on manual actuator is in
place.
❒ Test the alarm and LED functions by
pressing the diamond-shaped “PRESS TO
TEST” button on the face of the control
panel. The alarm should sound and all
LED’s should illuminate.
☞NOTE:
The “Push to Test” function will not cause a
system discharge.
Fig. 1: Fire Suppression Cylinder Inspection
AGENT CYLINDER
INSPECTION POINT
REAR STREETSIDE
FLUORESCENT
LIGHT PANEL
s070045a.wmf
4 of 5 Copyright © 2013 New Flyer
Industries Canada ULC SMB-123B
SERVICE MANUAL BULLETIN
SMB-123B
1.5. Six Month Preventive
Maintenance
1.5.1. Modular III or AVSN Fire Suppression
System (without gas detection)
Perform the following inspections and servicing
procedures every six months:
☞NOTE:
Refer to Amerex Installation, Operation,
and Maintenance Manuals No. 13980 and
16601 for specific requirements and procedures
❒ Visually inspect condition of all fire suppression
components.
❒ Service the agent cylinder(s).
❒ Service the discharge valve.
❒ Inspect pressure gauge on discharge
valve.
❒ Service the discharge network.
❒ Confirm that all nozzles are properly aimed
and all blow-off caps are installed.
❒ Service the distribution system components.
❒ Service and test the detection network.
❒ Test the agent cylinder pressure switch circuit.
❒ Test the backup battery function.
❒ Inspection condition of wiring and connectors.
❒ Check last recharge date on agent cylinder
inspection tag.
❒ Inspect and test Safe-IR Optical Flame
Detectors (infrared sensors), if equipped.
1.5.2. AVSN Fire Suppression & Gas
Detection System
Perform the following inspections and servicing
procedures on the fire suppression
system every six months:
☞NOTE:
Refer to Amerex Installation, Operation,
and Maintenance Manuals No. 13980 and
16601 for specific requirements and procedures
❒ Visually inspect condition of all fire suppression
components.
❒ Service the agent cylinder(s).
❒ Service the discharge valve.
❒ Inspect pressure gauge on discharge
valve.
❒ Service the discharge network.
❒ Confirm that all nozzles are properly aimed
and all blow-off caps are installed.
❒ Service the distribution system components.
❒ Service and test the detection network.
❒ Test the agent cylinder pressure switch circuit.
❒ Test the backup battery function.
❒ Inspection condition of wiring and connectors.
❒ Check last recharge date on agent cylinder
inspection tag.
❒ Inspect and test Safe-IR Optical Flame
Detectors (infrared sensors), if equipped.
❒ Inspect and test the gas sensors every six
months.
☞NOTE:
Refer to Amerex Installation, Operation,
and Maintenance Manual No. 16601 for
specific requirements and procedures
SMB-123B Copyright © 2013 New Flyer
Industries Canada ULC 5 of 5
SERVICE MANUAL BULLETIN
SMB-123B
1.6. Three Year Preventive
Maintenance
1.6.1. Modular III Fire Suppression System
Replace the backup battery located inside
the fire suppression control panel every
three years. See “Fig. 2: Battery Replacement
Location” on page 5.
Fig. 2: Battery Replacement Location
1.6.2. AVSN Fire Suppression System
Replace the backup battery located inside
the fire suppression Driver Panel every
three years.
1. Set the Battery Disconnect swtich to the
OFF position.
2. Remove the access panel directly above
the driver’s side window.
3. Disconnect electrcal harnesses from the
Driver Panel.
4. Remove the four screws that mount the
Driver Panel to the mounting bracket.
5. Access the backside of the Driver Panel
and remove the four cover screws.
6. Remove backup battery.
7. Installation is the reverse of removal.
1.7. Six Year Preventive Maintenance
1.7.1. Modular III or AVSN Fire Suppression
System
Replace the electric actuator, located on
the discharge valve, following every six
years of service.
☞NOTE:
Refer to Amerex Installation, Operation,
and Maintenance Manual No. 16601 for
specific requirements and procedures.
????????????????????????????????????????????????????????????????????????????????
????????????????????
????????????????????????????????????????????????????????
s073716a.svg
SMB123_B
SMB123
- PROTECT YOUR PROPERTY AND LOVED ONES – Designed specifically for residential kitchens with four-burner stoves, the Rangehood Fire Suppressor offers essential protection against cooking fires. Tested and approved for grease fires, it automatically activates to quickly suppress flames caused by grease.
- EASY TO INSTALL & AUTOMATICALLY ACTIVATED – Installs quickly under your range hood with included magnets. When exposed to direct sustained flame contact, it activates automatically, releasing a fire-suppressing agent for fast, effective protection.
- TARGETED KITCHEN FIRE PROTECTION – Built for residential stovetops, this automatic fire suppressor responds to cooking fires, releasing a fire-suppressing dry-powder for fast, reliable protection right where it’s needed most.
- LOW MAINTENANCE & LONG-LASTING – With a 6-year effective life, these fire suppressors need no upkeep or maintenance required. They activate only during a fire and leave minimal, non-toxic residue, making them a hassle-free safety solution for any kitchen.
- TRUSTED FIRE SAFETY SOLUTION – Proven effective in preventing fires and saving lives, this reliable fire suppression system offers peace of mind & safety. Easy to install and use—don’t wait until it’s too late to protect your kitchen and loved ones.
- Reliable Fire Protection: Stop basic home fires involving trash, wood, paper, liquids, gases, and electrical equipment
- All-Metal Construction: Made with robust materials for long-lasting durability
- Easy pull safety pin
- Compact & Lightweight: Aluminum construction and small size allow for easy storage and use
- Easy-to-Read Pressure Indicator: If arrow is in the green it’s charged
- Simple, Fast Activation:Take control with an easy-to-use design—just press, aim, and spray. Each extinguisher Emergency Survival Kits includes two sturdy mounting brackets for quick access in kitchens, cars, and other essential spots.
- Versatile 8-in-1 Fire Protection:Effectively tackles a variety of fires: wood, cooking oils, gasoline, and lithium-ion battery fires in devices like phones and laptops. A protective barrier helps prevent reignition for added security.
- Eco-Friendly and Non-Toxic Formula:The non-toxic, water-based formula is safe for users and the environment. It leaves no residue, making cleanup fast and mess-free—perfect for homes, vehicles, or offices.
- Compact and Portable:Lightweight and easy to store, this extinguisher fits into small spaces like kitchen drawers, glove compartments, or boat lockers, ensuring you’re prepared for emergencies anytime.
- Reliable 6-Year Warranty :Enjoy peace of mind with a six-year warranty. Whether it’s support, replacement, or guidance, the customer service team is ready to assist, keeping you safe and covered.
- PREPARED HERO EMERGENCY FIRE BLANKET: Extinguish small fires quickly and easily with no mess (unlike common fire extinguishers). Simply deploy the blanket by pulling down the tabs.
- PREPARED HERO PEACE OF MIND: Peace of mind for when fire happens from the brand you trust. Keep the Fire Blanket in the kitchen, backyard, vehicle or take it camping. It has a hole slot so it can also be easily hung on walls.
- LIGHTWEIGHT FIRE SUPPRESSION BLANKET: Effective on liquid or grease fires. It Works in different types of fire as well. They can also be used as a thermal or heat shield . A must have in your kitchen, backyard and vehicle survival kit for protection.
- NO MESS IN KITCHEN: Made from 100% quality flame retardant material. They conform to CE safety standards (EN 1896:1997). Composed of two layers of woven fiberglass fabric and an inner layer of fire retardant film. They can isolate high temperatures up to 1076°F (580℃).
- DOES NOT EXPIRE: Unlike traditional extinguishers, the fire blanket never expires. That means unlike traditional fire extinguishers, it doesn’t need to be replaced.
- ✔ INSTANT FIRE SUPPRESSION AT 170ºC ±10ºC (356°F) – The Ferosticker F01 activates automatically at 170ºC ±10ºC (356°F), releasing an aerosol that instantly suppresses fire by disrupting combustion, providing fast, automatic fire protection for enclosed spaces with a protected volume of 0.1 m³ (3.5 ft³). It is specifically designed for small confined spaces.
- ✔ NO ELECTRICITY, PRESSURE, OR WIRING REQUIRED – Unlike traditional extinguishers, the Ferosticker operates without batteries or cables. Its self-activating system ensures hassle-free fire safety with no maintenance required. Versatile protection: effective on fire classes A, B, C, E, and F, covering a wide range of fire risks.
- ✔ INSTALLS IN SECONDS – NO TOOLS NEEDED – Simply stick it in place, and the Ferosticker F01 is ready to protect. Designed for quick, effortless installation, it works in electric panels, lithium battery storage, fuse boxes, solar generators, and more.
- ✔ LONG-LASTING, MAINTENANCE-FREE PROTECTION – Once installed, this automatic fire extinguisher works for up to 6 years, requiring zero maintenance, refills, or inspections, just set it and forget it. It is also 3–10 times more effective than Halon and CO₂, providing superior long-term fire suppression.
- ✔ COMPACT & ECO-FRIENDLY FIRE SAFETY – Smaller than a marker and weighing only 19 g (0.67 oz), the Ferosticker F01 fits anywhere, making it perfect for homes, vehicles, boats, RVs, and confined spaces. Non-toxic, residue-free, and safe for electronics. Ideal for protecting valuable assets and preventing fire damage.
Last update on 2026-06-19 / Affiliate links / Images from Amazon Product Advertising API
This product presentation was made with AAWP plugin.